Introduction

Device Management app is used to calibrate, reboot, and update Nwave devices via BLE. Some of these operations are used in the Splace and Replace applications which allow you to manage installations(deployment) and replacements. The application requires an internet connection to make this process secure. User management configuration allows limiting which operations and on which devices each user(client can have multiple users with different permissions to different projects) can perform. Generally, you need to be not farther than 10 meters from a device to interact with it in the app.

Installation

At the moment, only Android version is available. You can download it at Google Play Store (https://play.google.com/store/apps/details?id=io.nwave.devicemanagement).

Login

To log in to the app you must first create an account in d.nwave.io using PIN-code which was provided to you. After that, you can use the same credentials in the app.

Application view

Image RemovedImage Added

  1. List of devices on which you can perform different actions

  2. Button to scan nearby BLE devices, only Nwave devices will be shown

  3. Button to add devices by their serial number.

  4. Button to scan QR code to add a device to the list

  5. Button to enter box number to add all sensors from the box to the list

  6. Button to Open options menu

  7. Pop-up menu with available actions for the selected device(click on device record to open the menu)

The application allows you to perform different actions to sensors added to the list (6). You can add sensors to the list by scanning nearby BLE devices(2), by scanning QR code on the device(4), by manually entering the device’s serial number(3), by entering box number(especially suitable for in-box firmware update).

Device record on the list shows you:

  • serial number

  • type of device

  • firmware name/ version

  • status of the last operation(the record becoming green after successful command completion)

Calibration

Calibration of parking sensors should be done when the parking space is free. The sensors perform continuous self-calibration and after some time will become fully calibrated even if the calibration was performed on an occupied sensor.

To initiate calibration just add a sensor to the list, click on the sensor’s record and press Calibrate in the pop-up menu.